We are using cookies to give you the best experience on our site. Cookies are files stored in your browser and are used by most websites to personalise your navigation. By clicking the Accept button or continuing to browse, you agree with our use of cookies. Click here for more information.
GM International
Log in or Sign up |          


Products:
 

D5040S

Code:

D5040S

Products comparison or request a quotation
Name:

SIL 3 Digital Output Driver, NE Loads, Loop Powered

Type:

Digital Output

Show similar products
Supply:

Loop Powered

Field device:

Show similar products
Channels:

1 (2 channels: D5040D)

Description:

The single channel Loop Powered Digital Output Isolator D5040S is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from driving signals in Safe Area. It can also be used as controllable supplies to power measuring or process control equipment.
Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. The Safety PLC or DCS driving signals control the field devices through D5040S , which provide isolation.
For each channel two basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the two output characteristics is obtained by connecting the field device to a different couple of terminal blocks.
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area or in Zone 2.

Features:

• SIL 3 according to IEC 61508:2010 Ed. 2 for lifetime = 20 yrs
• PFDavg (1 year) 0.00 E+00, SFF 100 %.
• Output to Zone 0 (Zone 20), installation in Zone 2.
• Loop powered for NE loads.
• Output short circuit proof and current limited.
• Two port isolation, Input/Output.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety systems.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks, or customized Termination Boards.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.

SIL level:

SIL 3

Data sheet:
DTS0524 D5040S data sheet (English) (PDF 327 KB)
Instruction manual:
ISM0121D5000-D5200 Series General Instruction Manual (PDF 3.27 MB)
ISM0187D5040S instruction manual (PDF 605 KB)
ISM0156D5000 Series Safety Instruction Manual (PDF 5.24 MB)
ISM0278UL Control Drawing for D5040S/D (PDF 100 KB)
Certifications:
CRT005UL & C-UL barriers listing [link E222308] (PDF 227 KB)
CRT126DNV Maritime Type Approval Certificate (D5000 Series) (PDF 1.68 MB)
CRT128TÜV SIL Certificate Summary (PDF 1.97 MB)
CRT130TÜV SIL Functional Safety Certificate (PDF 65 KB)
CRT153Korean Register Type Approval Certificate (PDF 1.22 MB)
CRT157ATEX Certificate n. BVS 14 ATEX E 159 X (PDF 3.54 MB)
CRT160IECEx CoC for D5040S, D5040D, D5240T [link IECEx BVS 14.0111X] (PDF 3.20 MB)
CRT218Ukraine certificate for D5000 series (PDF 2.80 MB)
CRT234Korea KCs certificate for D5040S (PDF 693 KB)
Accessories:
MCHP196Power Bus Terminal Block Cover and Fix
Various:
2D drawing of D5000 Series in DWG format (DWG 54 KB)
3D drawing of D5000 Series in DWG format (DWG 2.26 MB)
3D drawing of D5000 Series in STEP format (STEP 5.92 MB)
Conformal Coating Declaration (PDF 135 KB)
D5000 Dimensional Drawing (PDF 217 KB)
EU Declaration of Conformity DTS0619 (PDF 222 KB)
REACh, RoHS Declaration of Conformity (PDF 150 KB)
News: [Products] New Digital Output units: D5040S, D5040D, D5240T

D5040S - SIL 3 Digital Output Driver, NE Loads, Loop Powered

Click to enlarge
Are you interested in this product? Request a quotation, search for an expert in your area or contact us.


Home | Products | Download | Contacts | Site map
Products:
©

G.M. International srl

Via G. Mameli, 53-55
I-20852 Villasanta (MB)
ITALY
Tel: +39 039 2325038
Fax: +39 039 2325107

P. IVA / C.F. : 02312650969
REA: MI1418125
Cap. Soc.: 93600 €