Name:

5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition

Type:

Safety Relay

Show similar products
Supply:

24 Vdc nom (21.6 to27.6 Vdc)

Field device:

Show similar products
Channels:

1

Description:

The single channel Relay Output, D5091S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk industries. It provides isolation between input and output contacts.
Two mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.

D5091S provides 1 SPDT contact for two different safety functions:
1) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state)is available at Terminal Blocks 7-8. The driving signal is normally low (0 Vdc),the relay is normally de-energized, contact is open and load is de-energized. The safety function is met when the driving signal is high (24 Vdc),the relay is energized, contact is closed and load is energized. At Terminal Blocks 9-10 is also available a service contact (for service load) with opposite (not SIL) function.
2) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state)is available at Terminal Blocks 9-10. The driving signal is normally high (24 Vdc), the relay is normally energized, contact is open and load is de-energized. The safety function is met when the driving signal is low (0 Vdc), the relay is de-energized, contact is closed and load is energized. At Terminal Blocks 7-8 is also available a service contact (for service load) with opposite (not SIL) function.

Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.

Features:

• Systematic capability SIL 3
• Installation in Zone 2 / Division 2.
• 1 SPDT contact for 2 different Safety Functions:
1) SIL 3 for ND load (energized in fail safe state) with ND relay condition (energized in fail safe state)
2) SIL 3 for ND load (energized in fail safe state) with NE relay condition (de-energized in fail safe state)
• Line input monitoring in-field DIP Switch selectable.
• Driving input voltage monitoring.
• Input/Output isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.

SIL level:

SIL 3

Data sheet:
DTS0327 D5091S data sheet (English) (PDF 333 KB)
Instruction manual:
ISM0110D5091S instruction manual (PDF 637 KB)
ISM0121D5000-D5200 Series General Instruction Manual (PDF 3.27 MB)
ISM0164FM Control Drawing for D5090S, D5091S, D5290S, D5291S (PDF 116 KB)
ISM0156D5000 Series Safety Instruction Manual (PDF 5.24 MB)
Certifications:
CRT060ATEX certificate n. BVS 10 ATEX E 114 X (PDF 8.11 MB)
CRT062IECEx CoC for D5000 Series [link IECEx BVS 10.0072X] (PDF 8.31 MB)
CRT084Metrological Certificate for D5000 Series (Russia) (PDF 2.13 MB)
CRT110FM 3046304 (USA) & FM-C 3046304C (Canada) for D5000 Series (PDF 314 KB)
CRT126DNV Maritime Type Approval Certificate (D5000 Series) (PDF 1.68 MB)
CRT127INMETRO Certificate DNV 13.0109 X (PDF 619 KB)
CRT128TÜV SIL Certificate Summary (PDF 1.97 MB)
CRT130TÜV SIL Functional Safety Certificate (PDF 65 KB)
CRT136TRCU Certificate for D5000 Series (PDF 1.35 MB)
CRT153Korean Register Type Approval Certificate (PDF 1.22 MB)
CRT169NEPSI cert. no. GYJ14.1406X (PDF 6.93 MB)
CRT206UL & C-UL relays listing [link E477485] (PDF 67 KB)
CRT218Ukraine certificate for D5000 series (PDF 2.80 MB)
Application notes:
APN0037D5091S, D5294S (PDF 265 KB)
Accessories:
MCHP196Power Bus Terminal Block Cover and Fix
Various:
2D drawing of D5000 Series in DWG format (DWG 54 KB)
3D drawing of D5000 Series in DWG format (DWG 2.26 MB)
3D drawing of D5000 Series in STEP format (STEP 5.92 MB)
Conformal Coating Declaration (PDF 135 KB)
D5000 Dimensional Drawing (PDF 217 KB)
EU Declaration of Conformity DTS0371 (PDF 211 KB)
IECEx Declaration of conformity DTS0374 (PDF 133 KB)
REACh, RoHS Declaration of Conformity (PDF 150 KB)
News: [Certifications] D5000 Series first UL approvals for United States and Canada

D5091S - 5 A SIL 3 Relay Output Module for ND Load

Click to enlarge
Are you interested in this product? Request a quotation, search for an expert in your area or contact us.


Home | Products | Download | Contacts | Site map
Products:
©

G.M. International srl

Via G. Mameli, 53-55
I-20852 Villasanta (MB)
ITALY
Tel: +39 039 2325038
Fax: +39 039 2325107

P. IVA / C.F. : 02312650969
REA: MI1418125
Cap. Soc.: 93600 €